Technical Details

Technical Details

Aqueous water cleaning systems produce from 0.14 to 2.85 m3/hr pf high purity water.

The systems incorporate a range of mixed bed and carbon cylinders that are capable of operating at temperatures of 70­­°C.

System Performance

Model Deionisation Resin Activated Carbon
AQ1D AQ2D AQ5D AQ9D AQ10D AQ1C AQ2C AQ5C AQ9C AQ10C

Max Flow/∆P

l/h  600  1000  1800  1875  2835  600  1000  1800  1875  2835 

 

psi  8.0  10.0  15.0  12.5  30.0  7.0  7.0  10.0  6.0  15.0 

Min Flow/∆P

l/h  140  225  400  625  940  140  225  400  625  940 

 

psi  1.0  1.0  1.0  2.5  7.5  1.0  1.0  1.0  0.5  2.0 

Max Operating Pressure 

psi  70  70  70  90  90  70  70  70  90  90 

 

bar  4.8  4.8  4.8  6.0  6.0  4.8  4.8  4.8 6.0  6.0 

Max Temperature 

°C  70 70  70  70  70  70  70  70  70  70 

Capacity (output impurities)

m3 mg/l   163  360  640  1000  1500 

 Change carbon every other deioniser change unless otherwise recommended.

System Dimensions

Model Deionisation Resin Activated Carbon
AQ1D AQ2D AQ5D AQ9D AQ10D AQ1C AQ2C AQ5C AQ9C AQ10C

Height 

mm  700  1000  1000  1195  1600  710  1000  1000  1195  1600 

Diameter 

mm  185  200  263  320  320 185  200  263  320  320 

Weight 

kg  18  25  48  60  115  18  25  48  60  115 

Treated Water Quality

Model Conductivity Resistivity Silica Carbon Dioxide Trace Dissolved Metals Residual Solids Average pH
µS/cm MΩ-cm mg/l mg/l mg/l mg/l neutral
Aquaclean™  1.0-0.1  1.0-10  <0.5  <0.5  <0.001  <0.5